Contact

buffer tank

JPSR 2000 · without insulation

JPSR Type 2000 · High-Performance Solar Buffer Tanks

Item No. 1112000

  • Tanks without insulation
nominal capacity
1981
Ø without insulation
1,100 mm
Height
2,370 mm
Weight
264 kg
Tank 1112000 Delivery time: approx. 4–6 weeks

As of Oct 28, 2026

Request for 1112000

EAN 4250659500611

Average of JPSR Type 2000

Dimensions and weights

H 2,370 Ø 1,100 K I H G J F E
Ø without insulation
1,100 mm
Height
2,370 mm
tilt height
2,420 mm
Weight
264 kg

Connections

Letters as shown in the illustration

Letter connection Height Size Thread Angle
E Connection 1 320 mm 1½" Female thread 10°
E Connection 1 320 mm 1½" Female thread 110°
E sensor sleeve 320 mm ½" Female thread 94.37°
K Heating Return Index RL 320 mm 1¼" Female thread 25.63°
F Connection 2 900 mm 1½" Female thread 10°
F Connection 2 900 mm 1½" Female thread 110°
F sensor sleeve 900 mm ½" Female thread 94.37°
J Heating flow line Index flow 1,120 mm 1¼" Female thread 25.63°
G Connection 3 1,490 mm 1½" Female thread 10°
G Connection 3 1,490 mm 1½" Female thread 110°
G sensor sleeve 1,490 mm ½" Female thread 94.37°
H Connection 4 2,020 mm 1½" Female thread 10°
H Connection 4 2,020 mm 1½" Female thread 110°
H sensor sleeve 2,020 mm ½" Female thread 94.37°
I Top connection 2,370 mm 1½" Female thread 0°

Technical Specifications

Volume

nominal capacity
1981

heat exchanger

Heat exchanger Bottom Surface
4.2 m²

Print

Operating pressure of storage tanks
3 bar
Test pressure of the storage tank
4.5 bar
Max. Pressure heat exchanger
6 bar

specification text

ENERGY BUFFER TANK

Buffer tank for all hot water central heating systems. Suitable for: solid fuel and oil-fired boilers, heat pumps, solar systems, and gas or electric instantaneous water heaters. Manufactured from high-quality S235JR steel in accordance with EN 10025 and EC Directive 97/23/EC; exterior with anti-corrosion coating, interior left unfinished. Includes a sensor terminal strip for variable positioning of the sensors.

Nominal capacity
1981 L
Operating pressure of storage tanks
3 bar
Test pressure of the storage tank
4.5 bar
Minimum pressure in the storage tank
+0 bar
Max. operating temperature
95°C
Min. temperature
20 °C
Heat exchanger Bottom Surface
4.2 m²
Max. Pressure heat exchanger
6 bar

Features

  • 4 x 1½" sockets (system connection on the left)
  • 4 x 1½" sockets (system connection on the right)
  • System connections, including layer baffle plate
  • 1 x 1½" socket (air vent)
  • 4 x ½" sockets (standard sockets)
  • 2 x 1" Socket (heat exchanger)

The system connection ports are spaced 100° apart. Dimensions without insulation: 1100 x 2370 (Ø x H) mm

Manufacturer
Juratherm GmbH
Match Code
JPSR 2000
Weight
~264 kg
Tilt height
2420 mm
EAN13
4250659500611

Product video

JPSR 2000 in motion