buffer tank
JPSM 300 · Neodul® silver
Efficiency Class B
JPSM Type 300, assembled, silver · Includes 100 mm Neodul® insulation
Item No. 840333
- heat loss
- 64 W
- Standby loss
- 1.54 kWh/24 h
- ErP Volume
- 279
- Weight
- 64 kg
As of Oct 28, 2026
EAN 4250659510108
Dimensions and weights
- Ø with insulation
- 810 mm
- Ø without insulation
- 550 mm
- Height including insulation
- 1,450 mm
- Height without insulation
- 1,350 mm
- tilt height
- 1,385 mm
- Installation dimensions
- 610 mm
- Weight
- 64 kg
- Insulation thickness
- 100 mm
Connections
Letters as shown in the illustration
| Letter | connection | Height | Size | Thread | Angle |
|---|---|---|---|---|---|
| E | Connection 1 | 220 mm | 1½" | Female thread | 20.8° |
| E | Connection 1 | 220 mm | 1½" | Female thread | 120.8° |
| E | sensor sleeve Sensor for Connection 1 | 220 mm | ½" | Female thread | 89.53° |
| F | Connection 2 | 470 mm | 1½" | Female thread | 20.8° |
| F | Connection 2 | 470 mm | 1½" | Female thread | 120.8° |
| F | sensor sleeve Sensor for Connection 2 | 470 mm | ½" | Female thread | 89.53° |
| G | Connection 3 | 800 mm | 1½" | Female thread | 20.8° |
| G | Connection 3 | 800 mm | 1½" | Female thread | 120.8° |
| G | sensor sleeve Sensor for Connection 3 | 800 mm | ½" | Female thread | 89.53° |
| H | Connection 4 | 1,120 mm | 1½" | Female thread | 20.8° |
| H | Connection 4 | 1,120 mm | 1½" | Female thread | 120.8° |
| H | sensor sleeve Sensor for connection 4 | 1,120 mm | ½" | Female thread | 89.53° |
| I | Top connection | 1,350 mm | 1½" | Female thread | 0° |
Technical Specifications
Volume
- nominal capacity
- 279
- Operating pressure of storage tanks
- 4.5 bar
- Test pressure of the storage tank
- 7.8 bar
insulation
- Insulation thickness of the jacket (assembled)
- 100 mm
- Insulation color
- silver
- Fire rating
- B2 according to DIN 4102
Energy (ErP)
- ErP Class
- B
- ErP - Heat loss (W)
- 64 W
- ErP – Heat Loss (kWh)
- 1.54 kWh
- ErP - Contents
- 279
Miscellaneous
- Installation dimensions
- 610 mm
specification text
ENERGY BUFFER TANK incl. insulation
Buffer tank for all hot water central heating systems. Suitable for: solid fuel and oil-fired boilers, heat pumps, solar systems, and gas or electric instantaneous water heaters. Manufactured from high-quality S235JR steel in accordance with EN 10025 and EC Directive 97/23/EC; exterior with anti-corrosion coating, interior left unfinished. Includes a sensor terminal strip for variable positioning of the sensors.
- Nominal capacity
- 279 L
- Operating pressure of storage tanks
- 4.5 bar
- Test pressure of the storage tank
- 7.8 bar
- Minimum pressure in the storage tank
- +0 bar
- Max. operating temperature
- 95°C
- Min. temperature
- 20 °C
Features
- 4 x 1½" sockets (system connection on the left)
- 4 x 1½" sockets (system connection on the right)
- System connections, including layer baffle plate
- 1 x 1½" socket (air vent)
- 4 x ½" sockets (standard sockets)
The system connection ports are spaced 100° apart.
Insulation Details
- Material
- Neodul®
- Insulation color
- Silver
- Fire rating
- B2 according to DIN 4102
- Temperature Resistance
- 110 °C
- ErP Class
- B
- ErP - Heat loss (W)
- 64 W
Insulation thickness of jacket (assembled): 100 mm (80 mm gray EPS, 0.032 W/mK; 20 mm polyester fiber fleece, 0.040 W/mK)
Cover thickness 150 mm
- 100 mm EPS, gray, 0.032 W/mK
- 50 mm polyester fiber fleece 0.040 W/mK
Floor insulation made of high-density fleece
- 50 mm polyester fiber fleece 0.033 W/mK
Dimensions with insulation
- 810 x 1450 (Ø x H) mm
- Manufacturer
- Juratherm GmbH
- Match Code
- JPSM 300 mont Silver Neodul®
Assembly consisting of
- JPSM Type 300
- Neodul Insulation Type 300
- Weight
- ~64 kg
- Tilt height
- 1385 mm
- EAN13
- 4250659510108
Composition
- 110300 JPSM Type 300 tank · High-Performance Buffer Tanks
- 9720300 Neodul Insulation Type 300 insulation · JPSM/R/RR + JPSL/R/RR + JH/S/SS 100 mm silver