Contact

buffer tank

JPSLR 2000 · Ecoline Vlies silver

Efficiency Class C

JPSLR Type 2000 V2, assembled, silver · Includes 130 mm fleece insulation

Item No. 840439

  • Assembled tank
  • Not included in the price list
heat loss
166 W
Standby loss
3.99 kWh/24 h
ErP Volume
2,010
Weight
199 kg
Tank 1572000 Delivery time: approx. 4–6 weeks
Insulation 9972000 In stock
Total Delivery time: approx. 4–6 weeks

As of Oct 28, 2026

Request for 840439

EAN 4250659513307

Average of JPSLR Type 2000 V2, assembled, silver

Dimensions and weights

H 2,470 Ø 1,360
Ø with insulation
1,360 mm
Ø without insulation
1,100 mm
Height including insulation
2,470 mm
Height without insulation
2,370 mm
tilt height
2,420 mm
Weight
199 kg
Insulation thickness
130 mm

Connections

No connections have been specified for this tank yet.

Technical Specifications

Volume

nominal capacity
1981

heat exchanger

Heat exchanger Bottom Surface
4.2 m²
WT Content at the bottom
27.5

Print

Heat exchanger Pressure drop at the bottom
372 mbar
Operating pressure of storage tanks
3 bar
Test pressure of the storage tank
4.5 bar
Max. Pressure heat exchanger
6 bar

insulation

Insulation thickness of the jacket (assembled)
130 mm
Insulation thickness of the jacket (raw)
145 mm
Insulation thickness of the lid
150 mm
Insulation color
silver
Lambda
0.0388 W/mK
Bulk density
2340 g/m²
Fire rating
B2 according to DIN 4102

Energy (ErP)

ErP Class
C
ErP - Heat loss (W)
166 W
ErP – Heat Loss (kWh)
3.99 kWh
ErP - Contents
2010

specification text

ENERGY BUFFER TANK with 1 heat exchanger, including insulation with a stratification charging system, resulting in significantly improved stratification behavior

Buffer tank for all hot water central heating systems. Suitable for: solid fuel and oil-fired boilers, heat pumps, solar systems, and gas or electric instantaneous water heaters. Manufactured from high-quality S235JR steel in accordance with EN 10025 and EC Directive 97/23/EC; exterior with anti-corrosion coating, interior left unfinished. Includes a sensor terminal strip for variable positioning of the sensors.

Nominal capacity
1981 L
Operating pressure of storage tanks
3 bar
Test pressure of the storage tank
4.5 bar
Minimum pressure in the storage tank
+0 bar
Max. operating temperature
95°C
Min. temperature
20 °C
Heat exchanger Bottom Surface
4.2 m²
WT Content at the bottom
27.5 L
Heat exchanger Pressure drop at the bottom
372 mbar
Max. Pressure heat exchanger
6 bar

Features

  • 1 x 1½" socket (air vent)
  • 5 x 2" socket (system connection on the left)
  • 5 x 2" sockets (system connection on the right)
  • 2 x deflector plates
  • 2 x mitered pipe DN 50
  • 2 x return layer ducts
  • 5 x ½" sockets (standard sockets)
  • 1 x perforated sheet, 50%
  • 2 x 1" Socket (heat exchanger)

The system connection ports are spaced 100° apart.

Insulation Details

Material
Polyester fiber nonwoven
Insulation color
Silver
Insulation thickness of the jacket (assembled)
130 mm
Lambda
0.0388 W/mK
Fire rating
B2 according to DIN 4102
Temperature Resistance
110 °C
Bulk density
2340 g/m²
Includes 50 mm floor insulation
ErP Class
C
ErP - Heat loss (W)
166 W

Dimensions with insulation

  • 1360 x 2470 (Ø x H) mm
Manufacturer
Juratherm GmbH
Match Code
JPSLR 2000 V2 silver

Assembly consisting of

  • JPSLR Type 2000 V2
  • Fleece insulation Type 2000
Weight
~199 kg
Tilt height
2420 mm
EAN13
4250659513307

Composition

Product video

JPSLR 2000 in motion